Product catalogue 2026, with every datasheetDownload

Low-voltage power cable

NYY Multi-core power cable, sector conductors

CU / PVC / PVC

NYY, layers stripped back
Rated voltage
0.6/1 kV
Reference standard
ISIRI 3569-1IEC 60502-1
Designation
NYY
Layer structure
CU / PVC / PVC
  • CUCopper conductor
Max. conductor temperature
70 °C

کاربرد

Application

For power distribution in open air, underground, indoors, in cable ducts and in power stations, where mechanical damage is not expected.

جدول مشخصات

Datasheet

NYY 3 × 50

CU / PVC / PVC

3D model of the cable's layers: NYY 3 × 50
  • Outer sheath⁦1.8 mm⁩
  • PVC insulation⁦1.4 mm⁩
  • Copper conductor

3D reconstruction from this table row. Press the cable to play it again.

NYY 3 × 50Schematic cross-section, approximate scale
Point at a row to see that size. Select it to rebuild the 3D model too.
Nominal cross-sectionmm²ClassInsulation thicknessmmSheath thicknessmmApprox. overall diametermmMax. conductor resistance at 20 °CΩ/kmApprox. weightkg/km
21.41.825.80.3871753
21.41.928.90.2682318
21.62.133.20.1933155
21.62.236.10.1533885
21.82.340.10.1244802
22.02.444.10.09915933
22.22.649.80.07547773
22.42.954.50.06019600
21.4 , 1.21.927.40.387 , 0.7271965
21.4 , 1.22.030.60.268 , 0.524—†
21.6 , 1.42.235.20.193 , 0.387—†
21.6 , 1.42.338.20.153 , 0.2684577
21.8 , 1.42.441.60.124 , 0.2685486
22.0 , 1.62.645.80.0991 , 0.1936869
22.2 , 1.62.6520.0754 , 0.1538957
21.41.929.40.3872269
21.42.133.40.2683091
21.62.237.30.1934176
21.62.341.60.1535158
21.82.546.60.1246396
22.02.751.50.09917929
22.22.957.90.075410378
22.43.163.60.060112830

† under review

Table source: print page 31 of the 12 November 2023 edition (superseded by the 2026 edition)

This product in the catalogue (PDF)

Aluminium and copperwire and cable,from Kaveh Industrial City

Request a quoteTell us the size and length