Product catalogue 2026, with every datasheetDownload

Low-voltage power cable

N2XY Single-core power cable

CU / XLPE / PVC

N2XY, layers stripped back
Rated voltage
0.6/1 kV
Reference standard
ISIRI 3569-1IEC 60502-1
Designation
N2XY
Layer structure
CU / XLPE / PVC
  • CUCopper conductor
  • XLPECross-linked polyethylene
Max. conductor temperature
90 °C

کاربرد

Application

For power distribution in open air, underground, indoors, in cable ducts and in power stations, where mechanical damage to the cable is not expected.

N2XY, layer by layer from the inside out: copper conductor, XLPE insulation, outer sheath (PVC).

Designation N2XY: 2X = XLPE insulation, Y = outer sheath (PVC).

Conductor cross-sections in this page's datasheet: 4 to 500 mm².

N2XY is made to the Iranian national standard ISIRI 3569-1 and the international standard IEC 60502-1.

جدول مشخصات

Datasheet

N2XY 1 × 4

CU / XLPE / PVC

3D model of the cable's layers: N2XY 1 × 4
  • Outer sheath⁦1.4 mm⁩
  • XLPE insulation⁦0.7 mm⁩
  • Copper conductor

3D reconstruction from this table row. Press the cable to play it again.

N2XY 1 × 4Schematic cross-section, approximate scale
Point at a row to see that size. Select it to rebuild the 3D model too.
Nominal cross-sectionmm²ClassInsulation thicknessmmSheath thicknessmmApprox. overall diametermmMax. conductor resistance at 20 °CΩ/kmApprox. weightkg/km
10.71.46.44.6172
20.71.46.74.6176
10.71.46.93.0892
20.71.47.33.0898
10.71.47.71.83136
20.71.48.21.83147
20.71.49.21.15209
20.91.410.90.727312
20.91.4120.524412
211.413.60.387540
21.11.415.50.268749
21.11.517.60.1931027
21.21.519.30.1531265
21.41.621.50.1241565
21.61.623.80.09911952
21.71.726.70.07542539
21.81.829.50.06013048
221.933.20.0474024
22.2237.20.03665132

This product in the catalogue (PDF)

Aluminium and copperwire and cable,from Kaveh Industrial City

Request a quoteTell us the size and length