- Rated voltage
- 0.6/1 kV
- Reference standard
- ISIRI 3569-1IEC 60502-1
- Designation
- NAYY
- Layer structure
- AL / PVC / PVC
- ALAluminium conductor
- Max. conductor temperature
- 70 °C
کاربرد
Application
For energy supply in open air, underground, indoors, in cable ducts and in switchboards, where mechanical damage to the cable is not expected.
جدول مشخصات
Datasheet
NAYY 1 × 16
AL / PVC / PVC

3D reconstruction from this table row. Press the cable to play it again.
Point at a row to see that size. Select it to rebuild the 3D model too.
| Nominal cross-sectionmm² | Class | Insulation thicknessmm | Sheath thicknessmm | Approx. overall diametermm | Max. conductor resistance at 20 °CΩ/km | Approx. weightkg/km |
|---|---|---|---|---|---|---|
| 2 | 1 | 1.4 | 9.9 | 1.910 | 128 | |
| 2 | 1.2 | 1.4 | 11.6 | 1.200 | 180 | |
| 2 | 1.2 | 1.4 | 12.7 | 0.868 | 223 | |
| 2 | 1.4 | 1.4 | 14.5 | 0.641 | 288 | |
| 2 | 1.4 | 1.4 | 16.2 | 0.443 | —† | |
| 2 | 1.6 | 1.5 | 18.7 | 0.320 | 491 | |
| 2 | 1.6 | 1.5 | 20.3 | 0.253 | 585 | |
| 2 | 1.8 | 1.6 | 22.4 | 0.206 | 700 | |
| 2 | 2 | 1.7 | 25 | 0.164 | 874 | |
| 2 | 2.2 | 1.8 | 28 | 0.125 | 1103 | |
| 2 | 2.4 | 1.9 | 31.3 | 0.100 | 1370 | |
| 2 | 2.6 | 2 | 34.9 | 0.078 | 1730 | |
| 2 | 2.8 | 2.1 | 38.6 | 0.061 | 2135 |
† under review
Table source: print page 17 of the 12 November 2023 edition (superseded by the 2026 edition)
همخانواده
Low-voltage power cable
NYY Single-core power cableN2XY Single-core power cableNA2XY Single-core power cableNYY Multi-core power cable, round conductorsNAYY Multi-core power cable, round conductorsN2XY Multi-core power cable, round conductorsNA2XY Multi-core power cable, round conductorsNYY Multi-core power cable, sector conductorsNAYY Multi-core power cable, sector conductorsN2XY Multi-core power cable, sector conductorsNA2XY Multi-core power cable, sector conductors
Aluminium and copperwire and cable,from Kaveh Industrial City
Request a quoteTell us the size and length