Product catalogue 2026, with every datasheetDownload

Low-voltage power cable

NAYY Single-core power cable

AL / PVC / PVC

NAYY, layers stripped back
Rated voltage
0.6/1 kV
Reference standard
ISIRI 3569-1IEC 60502-1
Designation
NAYY
Layer structure
AL / PVC / PVC
  • ALAluminium conductor
Max. conductor temperature
70 °C

کاربرد

Application

For energy supply in open air, underground, indoors, in cable ducts and in switchboards, where mechanical damage to the cable is not expected.

جدول مشخصات

Datasheet

NAYY 1 × 16

AL / PVC / PVC

3D model of the cable's layers: NAYY 1 × 16
  • Outer sheath⁦1.4 mm⁩
  • PVC insulation⁦1 mm⁩
  • Aluminium conductor7 wires

3D reconstruction from this table row. Press the cable to play it again.

NAYY 1 × 16Schematic cross-section, approximate scale
Point at a row to see that size. Select it to rebuild the 3D model too.
Nominal cross-sectionmm²ClassInsulation thicknessmmSheath thicknessmmApprox. overall diametermmMax. conductor resistance at 20 °CΩ/kmApprox. weightkg/km
211.49.91.910128
21.21.411.61.200180
21.21.412.70.868223
21.41.414.50.641288
21.41.416.20.443—†
21.61.518.70.320491
21.61.520.30.253585
21.81.622.40.206700
221.7250.164874
22.21.8280.1251103
22.41.931.30.1001370
22.6234.90.0781730
22.82.138.60.0612135

† under review

Table source: print page 17 of the 12 November 2023 edition (superseded by the 2026 edition)

This product in the catalogue (PDF)

Aluminium and copperwire and cable,from Kaveh Industrial City

Request a quoteTell us the size and length