Product catalogue 2026, with every datasheetDownload

Low-voltage power cable

NAYY Multi-core power cable, sector conductors

AL / PVC / PVC

NAYY, layers stripped back
Rated voltage
0.6/1 kV
Reference standard
ISIRI 3569-1IEC 60502-1
Designation
NAYY
Layer structure
AL / PVC / PVC
  • ALAluminium conductor
Max. conductor temperature
70 °C

کاربرد

Application

For power distribution in open air, underground, indoors, in cable ducts and in power stations, where mechanical damage is not expected.

جدول مشخصات

Datasheet

NAYY 3 × 50

AL / PVC / PVC

3D model of the cable's layers: NAYY 3 × 50
  • Outer sheath⁦1.8 mm⁩
  • PVC insulation⁦1.4 mm⁩
  • Aluminium conductor

3D reconstruction from this table row. Press the cable to play it again.

NAYY 3 × 50Schematic cross-section, approximate scale
Point at a row to see that size. Select it to rebuild the 3D model too.
Nominal cross-sectionmm²ClassInsulation thicknessmmSheath thicknessmmApprox. overall diametermmMax. conductor resistance at 20 °CΩ/kmApprox. weightkg/km
21.41.825.80.641831
21.41.928.90.4431052
21.62.133.20.3201426
21.62.236.10.2531716
21.82.340.10.2062099
22.02.444.10.1642524
22.22.649.80.1253265
22.42.954.50.1003998
21.4 , 1.21.927.40.641 , 1.20928
21.4 , 1.22.030.60.443 , 0.8681189
21.6 , 1.42.235.20.32 , 0.6411637
21.6 , 1.42.338.20.253 , 0.4431986
21.8 , 1.42.441.60.206 , 0.4432361
22.0 , 1.62.645.80.164 , 0.3202887
22.2 , 1.62.652.00.125 , 0.2533726
21.41.929.40.6411093
21.42.133.40.4431403
21.62.237.30.3201884
21.62.341.60.2532266
21.82.546.60.2062796
22.02.751.50.1643385
22.22.957.90.1254370
22.43.163.60.1005260

Table source: print page 33 of the 12 November 2023 edition (superseded by the 2026 edition)

This product in the catalogue (PDF)

Aluminium and copperwire and cable,from Kaveh Industrial City