Product catalogue 2026, with every datasheetDownload

Low-voltage power cable

NA2XY Multi-core power cable, round conductors

AL / XLPE / PVC

NA2XY, layers stripped back
Rated voltage
0.6/1 kV
Reference standard
ISIRI 3569-1IEC 60502-1
Designation
NA2XY
Layer structure
AL / XLPE / PVC
  • ALAluminium conductor
  • XLPECross-linked polyethylene
Max. conductor temperature
90 °C

کاربرد

Application

For power distribution in open air, underground, indoors, in cable ducts and in power stations, where mechanical damage is not expected.

جدول مشخصات

Datasheet

NA2XY 2 × 10

AL / XLPE / PVC

3D model of the cable's layers: NA2XY 2 × 10
  • Outer sheath⁦1.8 mm⁩
  • Inner covering⁦1 mm⁩
  • XLPE insulation⁦0.7 mm⁩
  • Aluminium conductor

3D reconstruction from this table row. Press the cable to play it again.

NA2XY 2 × 10Schematic cross-section, approximate scale
Point at a row to see that size. Select it to rebuild the 3D model too.
Nominal cross-sectionmm²ClassInsulation thicknessmmInner covering thicknessmmSheath thicknessmmApprox. overall diametermmMax. conductor resistance at 20 °CΩ/kmApprox. weightkg/km
10.711.815.33.08300
20.711.816.23.08333
20.711.818.41.91442
20.911.821.71.20617
20.911.823.90.868762
10.711.8163.08335
20.711.8173.08370
20.711.819.41.91491
20.911.8231.20697
20.911.825.30.868862
10.711.817.33.08386
20.711.818.43.08426
20.711.8211.91570
20.911.825.11.20814
20.911.827.70.8681019
20.9 , 0.711.8241.20 , 1.91*752
20.9 , 0.711.8260.868 , 1.91*899

* corrected against the print catalogue

Table source: print page 29 of the 12 November 2023 edition (superseded by the 2026 edition)

This product in the catalogue (PDF)

Aluminium and copperwire and cable,from Kaveh Industrial City

Request a quoteTell us the size and length